How the checks work
Punching. The four interior columns each carry a 6 × 6 m tributary area. A circular perimeter sits 2d outside each column face. If the opening comes within 6d of the face, rays from the column centre through the opening discount the arc between the tangents. The readout follows the highest demand-to-capacity ratio.
V = q × 36 m²
Vᵣ = v × d × effective perimeter
Span. Two adjacent 3 m strips span 6 m between assumed support lines in one direction. Each keeps its full load. At the cut, its bending capacity falls in proportion to the width left. The model compares the peak moment within the cut with the intact midspan where present, then shows the governing strip and section.
M(x) = q × 3 m × x(6 m − x) / 2
Mᵣ = resistance per metre × net width
Modelled cut limit. For each trial width or length the model checks all four columns and both strips, keeping the other dimension fixed. Moving the cut or using a slider tests sizes about its current centre. Pulling a corner holds the opposite corner fixed and tests the dimension you change most. The search ends at the bay inset or 3.00 m. The displayed threshold is approximate. The pass or over result uses the unrounded checks.
The placement map samples 35 × 35 opening centres between the four columns. A 400 mm inset from the grid lines bounds the editable area.
The displayed floor is cropped from a repeating flat slab. Columns are 500 mm in diameter. The slab is 260 mm thick with 220 mm effective depth. Use the arrow keys on the model to move the opening by 0.10 m.
Assumed strengths and uniform loading. Two-way redistribution, deflection and reinforcement detailing are outside these checks. Illustrative, not a design tool.